Applications

It is designed for INSTABUS EIB data systems for building control systems to provide more comfort, security, energy saving. For lighting, heating, air conditioning, security systems ,remote control and tracing and data communication INSTABUS EIB cables can be used.

Cable Structure

Inner Conductor

Electrolytic Solid Copper Wire, Class 1, EN 60228

Insulation

HFFR Compound, EN 50290-2-26, VDE 0815 Colour Code

Stranding

Star Quad

Seperator

PES Tape

Screen

AL-PES Tape and Tinned Copper Drain Wire

Outer Sheath

HFFR Compound EN 50290-2-27, VDE 0207, RAL 6001 Green



Ürün Kodu Damar S./Kesit(mm²) Kablo Çapı(mm)(±5%) Bakır Ağ.(kg/km) ~Kablo Ağ.(kg/km) Standart Uzunluk


DC LOOP 
RESISTANCE
INSULATION 
RESISTANCE
MUTUAL 
CAPACITY (MAX)
OPERATING 
VOLTAGE
TEST 
VOLTAGE
BENDING 
RADIUS
TEMPERATURE 
RANGE
MM
0,8
Ω/Km
73,2
MΩ km
100
nF/k m
100
V
300
V
1000
10x D-30ºC+70ºC
FLAME RETARDANT TESTSMOKE DENSITY TESTTEST ON CORROSIVENESS
OF COMBUSTION
FLAME PROPOGATION
IEC 60332-1-2
VDE 0482-332-1-2
EN 60332-1-2
IEC 61034-2
VDE 0482-1034-2
EN 61034-2
IEC 60754-2
VDE 0482-267-2-3
EN 50267-2-3
IEC 60332-3-24
VDE 0482-332-3-24
EN 60332-2-24