Applications

These cables are used in the emergency circuits as signal and communication cables, which continue functioning during an instance of fire. (They are used atv places where a lot of people can be found such as subways, tunnels, shopping centers, hospitals, airports, hotels, residential buildings, industrial facilities etc.)

This type of cables is halogen-free, has flame -retarder and low smoke density.

Cable Structure

Inner Conductor

Electrolytic Stranded Copper Wire Class 5
EN 60228, IEC 60228, VDE 0295

Insulation

Special Silicone Compound, DIN 47100 Colour Code

Stranding

Cores Twisted in Layers

Seperator

PES Tape and Glass Fiber Tape

1.Screen

Al-PES Tape

2.Screen

Tinned Copper Wire Braiding

Outer Sheath

HFFR Compound EN 50290-2-27, RAL 2003 Orange

 

Ürün Kodu Damar S./Kesit(mm²) Kablo Çapı(mm)(±5%) Bakır Ağ.(kg/km) ~Kablo Ağ.(kg/km) Standart Uzunluk
33159402 2 x 0,50 5,60 14,63 36,93 100 / 500 / 1000
33159403 3 x 0,50 5,85 18,99 43,88 100 / 500 / 1000
33159404 4 x 0,50 6,50 24,14 56,13 100 / 500 / 1000
33159405 5 x 0,50 7,00 28,72 65,65 100 / 500 / 1000
33159406 6 x 0,50 7,50 34,11 75,68 100 / 500 / 1000
33159407 7 x 0,50 7,50 38,36 81,88 100 / 500 / 1000
33159408 8 x 0,50 8,25 43,78 94,00 100 / 500 / 1000
33159410 10 x 0,50 9,40 53,56 115,97 100 / 500 / 1000
33159502 2 x 0,75 6,10 19,81 45,14 100 / 500 / 1000
33159503 3 x 0,75 6,60 26,38 58,00 100 / 500 / 1000
33159504 4 x 0,75 7,10 33,26 70,00 100 / 500 / 1000
33159505 5 x 0,75 7,65 40,52 83,27 100 / 500 / 1000
33159506 6 x 0,75 8,25 47,88 96,84 100 / 500 / 1000
33159507 7 x 0,75 8,25 54,25 105,27 100 / 500 / 1000
33159508 8 x 0,75 9,35 61,95 126,12 100 / 500 / 1000
33159510 10 x 0,75 10,40 76,20 149,25 100 / 500 / 1000
33159602 2 x 1,00 6,50 24,19 53,22 100 / 500 / 1000
33159603 3 x 1,00 6,80 32,92 65,35 100 / 500 / 1000
33159604 4 x 1,00 7,35 42,37 80,10 100 / 500 / 1000
33159605 5 x 1,00 7,95 51,21 95,12 100 / 500 / 1000
33159606 6 x 1,00 8,55 60,83 110,96 100 / 500 / 1000
33159607 7 x 1,00 8,55 69,32 121,53 100 / 500 / 1000
33159608 8 x 1,00 9,65 79,11 144,63 100 / 500 / 1000
33159610 10 x 1,00 10,80 97,74 172,58 100 / 500 / 1000
33159702 2 x 1,50 7,40 33,27 70,37 100 / 500 / 1000
33159703 3 x 1,50 7,80 45,84 87,00 100 / 500 / 1000
33159704 4 x 1,50 8,45 59,47 108,00 100 / 500 / 1000
33159705 5 x 1,50 9,35 73,03 134,21 100 / 500 / 1000
33159706 6 x 1,50 10,10 86,53 156,50 100 / 500 / 1000
33159707 7 x 1,50 10,10 98,94 177,66 100 / 500 / 1000
33159708 8 x 1,50 11,25 112,45 198,83 100 / 500 / 1000
33159710 10 x 1,50 12,80 138,93 244,00 100 / 500 / 1000
33159802 2 x 2,50 8,30 51,10 93,99 100 / 500 / 1000
33159803 3 x 2,50 8,75 71,95 120,14 100 / 500 / 1000
33159804 4 x 2,50 9,70 93,89 156,22 100 / 500 / 1000
33159805 5 x 2,50 10,55 116,15 188,87 100 / 500 / 1000
33159806 6 x 2,50 11,45 137,33 222,83 100 / 500 / 1000
33159807 7 x 2,50 11,45 158,95 246,64 100 / 500 / 1000
33159808 8 x 2,50 12,95 181,53 292,00 100 / 500 / 1000
33159810 10 x 2,50 14,60 225,00 350,52 100 / 500 / 1000


LOOP
RESISTANCE
INSULATION
RESISTANCE
MUTUAL 
CAPACITANCE
CURRENT 
CARRYING 
CAPACITY
BENDING
RADIUS
TEST VOLTAGE 
(50 Hz 1 Min) 
CORE/CORE
OPERATING VOLTAGETEMPERATURE
RANGE
mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
Ω/km
79
56
39
26
19,5
13,3
7,98
MΩxKm
0,22 ve 0,34 mm² = 200
>0,50 mm² = 20
nF/km
120
mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
A
2,5
4,5
6,0
13
16
20
25
7,5X D0.22 ve 0.34 mm2 = 1200 V
>0.50 mm2 = 2000 V
0.22 ve 0.34 mm2 = 250 V
>0.50 mm2 = 300/500 V
-40ºC+90ºC